RECD Installation and Maintenance Guide

Maintenance · 6 min read · Trishul Kosmic Energy

Emission control device flange and mounting hardware being fitted to a diesel generator exhaust

An RECD only delivers what it promises if it is installed properly and maintained afterwards. This guide covers both, in the order they happen on site.

Part 1 — Installation

Mounting and support

An RECD is heavy, and it sits in a vibrating exhaust line. It needs its own support, not just a flange connection carrying the weight. A properly designed bracket or frame isolates the device from the exhaust pipe and keeps stress off the manifold.

Exhaust connection

Flanges must mate cleanly with a proper gasket. Welded modifications should be done by someone competent with thin-wall exhaust steel, and the inside of the joint should be clean — weld spatter left inside the pipe will end up on the filter face.

Orientation and flow direction

Inlet and outlet are not interchangeable. Confirm the flow arrow before anything is bolted up. Getting this wrong is the most common avoidable installation error.

Access for service

Leave enough clearance to open the access cover and slide the element out. If that means moving the device a metre along the wall, do it at installation stage — not after the first service is due.

Commissioning checks

  • Confirm no leaks at any joint with the generator running under load.
  • Record the clean back pressure reading — this becomes your baseline.
  • Check exhaust temperature against the device's rated limits.
  • Photograph the installation for the site file.

Part 2 — Maintenance

Follow the manufacturer's interval

The cleaning or replacement interval for the element comes from the product manufacturer and is adjusted for your running hours and fuel quality. Treat it as the minimum, not the ideal.

Watch back pressure

Rising back pressure is the clearest early signal that the element is loading. If you have a gauge, log it. If you do not, ask for a periodic reading during generator servicing. A sudden jump usually means either a heavily loaded filter or an engine problem producing excess smoke.

Clean or replace the element

Cleaning method depends on the element type — some are back-flushed or blown clean, others are replaced. Using the wrong method (high-pressure water on a medium that should stay dry, for example) can destroy an element that was still serviceable.

Keep the engine healthy

Injector faults, over-fuelling and late servicing all increase particulate output. An RECD is not a substitute for engine maintenance; it is an addition to it.

Keep records

Log every service with date, running hours, back pressure reading and action taken. If a compliance question ever arises, this record is what demonstrates that the equipment has been maintained.

Service support from us